ecoTEC plus 630 boiler tweaks

$
0
0
I’m interested in fine turning my ecoTEC plus 630 boiler - specifically D.0 CH (30) and D.77 HW (30) part load, D.19 pump config (2) and thoughts on D.78 HW flow temp (80C) plus any other boiler teaks – numbers in brackets are current settings. The system is the 630 with VR65 + VR10 charging a Gledhill Stainless Lite Indirect 300 ltr cylinder with 25kW primary. CH is via rads / towel rails and thermostatic rad valves with a potential load of 27kW – HW has priority. The heat loss calcs with 20% margin for intermittent heating and -1 outside temp is 21kW.

I have just swapped my VRC430 for a Nest 3 / OpenTherm / VR33 solution that appears to fully modulate the boiler in CH mode between 75C (upper limit adjustable in Nest app) and 35C – the lowest I have seen so far. It’s rare to see the boiler in anti-cycle mode. It’s been around -1 to 0C outside today and the flow temp has varied 38 to 42C ish for a stable 18C room temp. It will be mid 50s C this evening for 20C room temp. Nest 3 uses the Vaillant dual control feature for HW demand and the flow temp is set by D.78 - currently 80C (default).

The rads are all balanced and bled etc and the system works well – way more responsive now with the Nest 3. This really is fine tuning + a bit of fun and curiosity.